Fireye sbSeries
Modular burner control for low cost commercial/industrial burner applications
Description
The Fireye sbSeries Flame Safeguard Control is a compact, microprocessor based, modular burner management system designed to provide automatic ignition and continuous flame monitoring for commercial sizes of heating and process equipment firing any type of fuel. The sbSeries are tested to EN298 and CE-certified in compliance with the directives for gas fired appliances and electromagnetic compatibility. The control unit includes all the necessary digital logic and analog measuring circuitry to control the sequence and monitor the flame of single gas, oil or combination gas/oil burners. Three available control sequences are no-purge, purge, and modulation (air damper control). The part number specifies the various features such as the flame sensor type, no purge, purge, modulation, proof of air opening at start, and timings; thus the designer has control and protection against field tampering of critical sequences. LED indicators are available on the front of the unit that provide current operating status of the burner system including lockout alarm. A test jack is recessed into the front cover that provides real time reading of the connected flame sensor. This same test jack is also used to connect to an alpha-numeric display, SB510 or SB511. A push button provides reset from lockout condition as well as placing the unit in a check condition usable for pilot turn down test. The sbSeries flame safeguard control family are of plug-in design and available in models that operate at 120 VAC, 50/60 Hz and 230 VAC, 50/60 Hz making them universally acceptable.
120 VAC OPERATION - NO PURGE |
|
|
|
S1N1U000400RPA |
120 VAC, no purge, 10 sec PTFI, Intermittent pilot, UV amp, no post purge, recycle, sequence hold, reset on power |
|
|
S1N1F000400RPA |
120 VAC, no purge, 10 sec PTFI, Intermittent pilot, FR amp, no post purge, recycle, sequence hold, reset on power |
|
|
120 VAC OPERATION - WITH PURGE |
|
|
|
S1P1U005400RPA |
120 VAC, 5 sec purge, 10 sec PTFI, Intermittent pilot, UV amp, no post purge, recycle, sequence hold, reset on power |
|
|
S1P1F005400RPA |
120 VAC, 5 sec purge, 10 sec PTFI, Intermittent pilot, FR amp, no post purge, recycle, sequence hold, reset on power |
|
|
S1P1U030423RPA |
120 VAC, 30 sec purge, 10 sec PTFI, 5 sec MTFI, UV amp, 15 sec post purge, recycle, sequence hold, reset on power |
|
|
S1P1F030423RPA |
120 VAC, 30 sec purge, 10 sec PTFI, 5 sec MTFI, FR amp, 15 sec post purge, non-recycle, sequence hold, reset on power |
|
|
120 VAC OPERATION - WITH MODULATION |
|
|
|
S1M1U030423NPA |
120 VAC, 30 sec purge, 10 sec PTFI, 5 sec MTFI, UV amp, modulation, 15 sec post purge, non-recycle, sequence hold, reset on power |
|
|
S1M1U030423NFA |
120 VAC, 30 sec purge, 10 sec PTFI, 5 sec MTFI, UV amp, modulation, 15 sec post purge, non-recycle, pre-purge air check, reset on power |
|
|
S1M1F030423NPA |
120 VAC, 30 sec purge, 10 sec PTFI, 5 sec MTFI, FR amp, modulation, 15 sec post purge, non-recycle, sequence hold, reset on power |
|
|
S1M1F030423NFA |
120 VAC, 30 sec purge, 10 sec PTFI, 5 sec MTFI, FR amp, modulation, 15 sec post purge, non-recycle, pre-purge check, reset on power |
|
|
230 VAC OPERATION - NO PURGE |
|
|
|
S2N1U000400RPA |
230 VAC, no purge, 10 sec PTFI, Intermittent pilot, UV amp, no post purge, recycle, sequence hold, reset on power |
|
|
S2N1F000400RPA |
230 VAC, no purge, 10 sec PTFI, Intermittent pilot, FR amp, no post purge, recycle, sequence hold, reset on power |
|
|
230 VAC OPERATION - WITH PURGE |
|
|
|
S2P1U005400RPA |
230 VAC, 5 sec purge, 10 sec PTFI, Intermittent pilot, UV amp, no post purge, recycle, sequence hold, reset on power |
|
|
S2P1F005400RPA |
230 VAC, 5 sec purge, 10 sec PTFI, Intermittent pilot, FR amp, no post purge, recycle, sequence hold, reset on power |
|
|
S2P1U015223RPA |
230 VAC, 15 sec purge, 5 sec PTFI, 5 sec MTFI, UV amp, 15 sec post purge, recycle, sequence hold, reset on power |
|
|
S2P1U030223NFA |
230 VAC, 30 sec purge, 5 sec PTFI, 5 sec MTFI, UV amp, 15 sec post purge, non-recycle, 10 second air proving, reset on power |
|
|
S2P1U030223NPA |
230 VAC, 30 sec purge, 5 sec PTFI, 5 sec MTFI, UV amp, 15 sec post purge, non-recycle, sequence hold, reset on power |
|
|
S2P1U015423NPA |
230 VAC, 15 sec purge, 10 sec PTFI, 5 sec MTFI, UV amp, 15 sec post purge, non-recycle, sequence hold, reset on power |
|
|
S2P1U030423NPA |
230 VAC, 30 sec purge, 10 sec PTFI, 5 sec MTFI, UV amp, 15 sec post purge, non-recycle, sequence hold, reset on power |
|
|
S2P1F015223NPA |
230 VAC, 15 sec purge, 5 sec PTFI, 5 sec MTFI, FR amp, 15 sec post purge, non-recycle, sequence hold, reset on power |
|
|
S2P1F030223NPA |
230 VAC, 30 sec purge, 5 sec PTFI, 5 sec MTFI, FR amp, 15 sec post purge, non-recycle, sequence hold, reset on power |
|
|
S2P1F015423NPA |
230 VAC, 15 sec purge, 10 sec tfi, 5 sec MTFI, FR amp, 15 sec post purge, non-recycle, sequence hold, reset on power |
|
|
S2P1F030423NPA |
230 VAC, 30 sec purge, 10 sec PTFI, 5 sec MTFI, FR amp, 15 sec post purge, non-recycle, sequence hold, reset on power |
|
|
230 VAC OPERATION - WITH MOULATION |
|
|
|
S2M1U030223NPA |
230 VAC, 30 sec purge, 5 sec PTFI, 5 sec MTFI, UV amp, modulation, 15 sec post purge, non-recycle, sequence hold, reset on power |
|
|
S2M1U060223NPA |
230 VAC, 60 sec purge, 5 sec PTFI, 5 sec MTFI, UV amp, modulation, 15 sec post purge, non-recycle, sequence hold, reset on power |
|
|
S2M1U030423NPA |
230 VAC, 30 sec purge, 10 sec PTFI, 5 sec MTFI, UV amp, modulation, 15 sec post purge, non-recycle, sequence hold, reset on power |
|
|
S2M1U030443NPA |
230 VAC, 30 sec purge, 10 sec PTFI, 10 sec MTFI, UV amp, modulation, 15 sec post purge, non-recycle, sequence hold, reset on power |
|
|
S2M1U030423NFA |
230 VAC, 30 sec purge, 10 sec PTFI, 5 sec MTFI, UV amp, modulation, 15 sec post purge, non-recycle, pre-purge check, reset on power |
|
|
S2M1U030443NFA |
230 VAC, 30 sec purge, 10 sec PTFI, 10 sec MTFI, UV amp, modulation, 15 sec post purge, non-recycle, pre-purge check, reset on power |
|
|
S2M1F030223NPA |
230 VAC, 30 sec purge, 5 sec PTFI, 5 sec MTFI, FR amp, modulation, 15 sec post purge, non-recycle, sequence hold, reset on power |
|
|
S2M1F030423NPA |
230 VAC, 30 sec purge, 10 sec PTFI, 5 sec MTFI, FR amp, modulation, 15 sec post purge, non-recycle, sequence hold, reset on power |
|
|
S2M1F030443NPA |
230 VAC, 30 sec purge, 10 sec PTFI, 10 sec MTFI, FR amp, modulation, 15 sec post purge, non-recycle, sequence hold, reset on power |
|
|
S2M1F030423NFA |
230 VAC, 30 sec purge, 10 sec PTFI, 5 sec MTFI, FR amp, modulation, 15 sec post purge, non-recycle, pre-purge check, reset on power |
|
|
S2M1F030443NFA |
230 VAC, 30 sec purge, 10 sec PTFI, 10 sec MTFI, FR amp, modulation, 15 sec post purge, non-recycle, pre-purge check, reset on power |
|
|
WIRING BASES |
|
|
|
61-6990-1 |
Internal terminal base, metal |
|
SB-2301 |
61-6990-2 |
Internal terminal base, plastic |
|
SB-2301 |
61-6991-1 |
Exposed terminal base, metal |
|
SB-2301 |
61-6991-2 |
Exposed terminal base, PLASTIC |
|
SB-2301 |
61-6994 |
Modulation base |
|
SB-2301 |
61-7012-2 |
Replacement relay module for use in modulation wiring base |
|
SB-2301 |
FLAME SCANNERS FOR USE WITH SB SERIES |
|
|
|
UV7A4 |
Straight UV scanner, 4 ft flex conduit |
|
|
UV7A4W |
NEMA 4 UV Scanner, 4 ft flex conduit |
|
|
UV7R4 |
90 degree UV Scanner. 6 ft shielded cable |
|
|
UV7SC |
Self-check scanner |
|
|
59-504-010 |
10 foot cable for self-check scanner |
|
- |
69ND1-1000K4 |
Flame rod, 12" (15mm), 1/2" mount (Auburn P/N FRS-2-12 |
|
|
69ND1-1000K6 |
Flame rod, 18" (30.5mm), 1/2" mount (Auburn P/N FRS-2-18 |
|
|
69ND1-1000K8 |
Flame rod, 24" (61mm), 1/2" mount (Auburn P/N FRS-2-24 |
|
Power Supply:
- 120VAC (min. 102, max 132) 50/60 Hz.
- 230 VAC (min 196, max 253) 50/60 Hz.
Power Consumption: 12VA (internal consumption, excludes externally connected loads)
Shipping Weight (Approx): 3 lbs (1.4 kg)