Burner Management System | SB Series

Fireye sbSeries

Modular burner control for low cost commercial/industrial burner applications

Description

The Fireye sbSeries Flame Safeguard Control is a compact, microprocessor based, modular burner management system designed to provide automatic ignition and continuous flame monitoring for commercial sizes of heating and process equipment firing any type of fuel. The sbSeries are tested to EN298 and CE-certified in compliance with the directives for gas fired appliances and electromagnetic compatibility. The control unit includes all the necessary digital logic and analog measuring circuitry to control the sequence and monitor the flame of single gas, oil or combination gas/oil burners. Three available control sequences are no-purge, purge, and modulation (air damper control). The part number specifies the various features such as the flame sensor type, no purge, purge, modulation, proof of air opening at start, and timings; thus the designer has control and protection against field tampering of critical sequences. LED indicators are available on the front of the unit that provide current operating status of the burner system including lockout alarm. A test jack is recessed into the front cover that provides real time reading of the connected flame sensor. This same test jack is also used to connect to an alpha-numeric display, SB510 or SB511. A push button provides reset from lockout condition as well as placing the unit in a check condition usable for pilot turn down test. The sbSeries flame safeguard control family are of plug-in design and available in models that operate at 120 VAC, 50/60 Hz and 230 VAC, 50/60 Hz making them universally acceptable. 

120 VAC OPERATION - NO PURGE

 

 

 

S1N1U000400RPA

120 VAC, no purge, 10 sec PTFI, Intermittent pilot, UV amp, no post purge, recycle, sequence hold, reset on power

 

SB-2301

S1N1F000400RPA

120 VAC, no purge, 10 sec PTFI, Intermittent pilot, FR amp, no post purge, recycle, sequence hold, reset on power

 

SB-2301

120 VAC OPERATION - WITH PURGE

 

 

 

S1P1U005400RPA

120 VAC, 5 sec purge, 10 sec PTFI, Intermittent pilot, UV amp, no post purge, recycle, sequence hold, reset on power

 

SB-2301

S1P1F005400RPA

120 VAC, 5 sec purge, 10 sec PTFI, Intermittent pilot, FR amp, no post purge, recycle, sequence hold, reset on power

 

SB-2301

S1P1U030423RPA

120 VAC, 30 sec purge, 10 sec PTFI, 5 sec MTFI, UV amp, 15 sec post purge, recycle, sequence hold, reset on power

 

SB-2301

S1P1F030423RPA

120 VAC, 30 sec purge, 10 sec PTFI, 5 sec MTFI, FR amp, 15 sec post purge, non-recycle, sequence hold, reset on power

 

SB-2301

120 VAC OPERATION - WITH MODULATION

 

 

 

S1M1U030423NPA

120 VAC, 30 sec purge, 10 sec PTFI, 5 sec MTFI, UV amp, modulation, 15 sec post purge, non-recycle, sequence hold, reset on power

 

SB-2301

S1M1U030423NFA

120 VAC, 30 sec purge, 10 sec PTFI, 5 sec MTFI, UV amp, modulation, 15 sec post purge, non-recycle, pre-purge air check, reset on power

 

SB-2301

S1M1F030423NPA

120 VAC, 30 sec purge, 10 sec PTFI, 5 sec MTFI, FR amp, modulation, 15 sec post purge, non-recycle, sequence hold, reset on power

 

SB-2301

S1M1F030423NFA

120 VAC, 30 sec purge, 10 sec PTFI, 5 sec MTFI, FR amp, modulation,  15 sec post purge, non-recycle, pre-purge check, reset on power

 

SB-2301

230 VAC OPERATION - NO PURGE

 

 

 

S2N1U000400RPA

230 VAC, no purge, 10 sec PTFI, Intermittent pilot, UV amp, no post purge, recycle, sequence hold, reset on power

 

SB-2301

S2N1F000400RPA

230 VAC, no purge, 10 sec PTFI, Intermittent pilot, FR amp, no post purge, recycle, sequence hold, reset on power

 

SB-2301

230 VAC OPERATION - WITH PURGE

 

 

 

S2P1U005400RPA

230 VAC, 5 sec purge, 10 sec PTFI, Intermittent pilot, UV amp, no post purge, recycle, sequence hold, reset on power

 

SB-2301

S2P1F005400RPA

230 VAC, 5 sec purge, 10 sec PTFI, Intermittent pilot, FR amp, no post purge, recycle, sequence hold, reset on power

 

SB-2301

S2P1U015223RPA

230 VAC, 15 sec purge, 5 sec PTFI, 5 sec MTFI, UV amp, 15 sec post purge, recycle, sequence hold, reset on power

 

SB-2301

S2P1U030223NFA

230 VAC, 30 sec purge, 5 sec PTFI, 5 sec MTFI, UV amp, 15 sec post purge, non-recycle, 10 second air proving, reset on power

 

SB-2301

S2P1U030223NPA

230 VAC, 30 sec purge, 5 sec PTFI, 5 sec MTFI, UV amp, 15 sec post purge, non-recycle, sequence hold, reset on power

 

SB-2301

S2P1U015423NPA

230 VAC, 15 sec purge, 10 sec PTFI, 5 sec MTFI, UV amp, 15 sec post purge, non-recycle, sequence hold, reset on power

 

SB-2301

S2P1U030423NPA

230 VAC, 30 sec purge, 10 sec PTFI, 5 sec MTFI, UV amp, 15 sec post purge, non-recycle, sequence hold, reset on power

 

SB-2301

S2P1F015223NPA

230 VAC, 15 sec purge, 5 sec PTFI, 5 sec MTFI, FR amp, 15 sec post purge, non-recycle, sequence hold, reset on power

 

SB-2301

S2P1F030223NPA

230 VAC, 30 sec purge, 5 sec PTFI, 5 sec MTFI, FR amp, 15 sec post purge, non-recycle, sequence hold, reset on power

 

SB-2301

S2P1F015423NPA

230 VAC, 15 sec purge, 10 sec tfi, 5 sec MTFI, FR amp, 15 sec post purge, non-recycle, sequence hold, reset on power

 

SB-2301

S2P1F030423NPA

230 VAC, 30 sec purge, 10 sec PTFI, 5 sec MTFI, FR amp, 15 sec post purge, non-recycle, sequence hold, reset on power

 

SB-2301

230 VAC OPERATION - WITH MOULATION

 

 

 

S2M1U030223NPA

230 VAC, 30 sec purge, 5 sec PTFI, 5 sec MTFI, UV amp, modulation, 15 sec post purge, non-recycle, sequence hold, reset on power

 

SB-2301

S2M1U060223NPA

230 VAC, 60 sec purge, 5 sec PTFI, 5 sec MTFI, UV amp, modulation, 15 sec post purge, non-recycle, sequence hold, reset on power

 

SB-2301

S2M1U030423NPA

230 VAC, 30 sec purge, 10 sec PTFI, 5 sec MTFI, UV amp, modulation, 15 sec post purge, non-recycle, sequence hold, reset on power

 

SB-2301

S2M1U030443NPA

230 VAC, 30 sec purge, 10 sec PTFI, 10 sec MTFI, UV amp, modulation, 15 sec post purge, non-recycle, sequence hold, reset on power

 

SB-2301

S2M1U030423NFA

230 VAC, 30 sec purge, 10 sec PTFI, 5 sec MTFI, UV amp, modulation, 15 sec post purge, non-recycle, pre-purge check, reset on power

 

SB-2301

S2M1U030443NFA

230 VAC, 30 sec purge, 10 sec PTFI, 10 sec MTFI, UV amp, modulation, 15 sec post purge, non-recycle, pre-purge check, reset on power

 

SB-2301

S2M1F030223NPA

230 VAC, 30 sec purge, 5 sec PTFI, 5 sec MTFI, FR amp, modulation, 15 sec post purge, non-recycle, sequence hold, reset on power

 

SB-2301

S2M1F030423NPA

230 VAC, 30 sec purge, 10 sec PTFI, 5 sec MTFI, FR amp, modulation, 15 sec post purge, non-recycle, sequence hold, reset on power

 

SB-2301

S2M1F030443NPA

230 VAC, 30 sec purge, 10 sec PTFI, 10 sec MTFI, FR amp, modulation, 15 sec post purge, non-recycle, sequence hold, reset on power

 

SB-2301

S2M1F030423NFA

230 VAC, 30 sec purge, 10 sec PTFI, 5 sec MTFI, FR amp, modulation, 15 sec post purge, non-recycle, pre-purge check, reset on power

 

SB-2301

S2M1F030443NFA

230 VAC, 30 sec purge, 10 sec PTFI, 10 sec MTFI, FR amp, modulation, 15 sec post purge, non-recycle, pre-purge check, reset on power

 

SB-2301

WIRING BASES 

 

 

 

61-6990-1

Internal terminal base, metal

 

SB-2301

61-6990-2

Internal terminal base, plastic

 

SB-2301

61-6991-1

Exposed terminal base, metal

 

SB-2301

61-6991-2

Exposed terminal base, PLASTIC

 

SB-2301

61-6994

Modulation base

 

SB-2301

61-7012-2

Replacement relay module for use in modulation wiring base

 

SB-2301

FLAME SCANNERS FOR USE WITH SB SERIES

 

 

 

UV7A4

Straight UV scanner, 4 ft flex conduit

 

SC-107

UV7A4W

NEMA 4 UV Scanner, 4 ft flex conduit

 

SC-107

UV7R4

90 degree UV Scanner. 6 ft shielded cable

 

SC-107

UV7SC

Self-check scanner

 

SC-107

59-504-010

10 foot cable for self-check scanner

 

-

69ND1-1000K4

Flame rod, 12" (15mm), 1/2" mount (Auburn P/N FRS-2-12

 

SC-103

69ND1-1000K6

Flame rod, 18" (30.5mm), 1/2" mount (Auburn P/N FRS-2-18

 

SC-103

69ND1-1000K8

Flame rod, 24" (61mm), 1/2" mount (Auburn P/N FRS-2-24

 

SC-103

Power Supply: 

  • 120VAC (min. 102, max 132) 50/60 Hz.
  • 230 VAC (min 196, max 253) 50/60 Hz.

Power Consumption: 12VA (internal consumption, excludes externally connected loads)

Shipping Weight (Approx): 3 lbs (1.4 kg)