sea

Flame Scanner Amplifier | 70D40 | Lias Industrial

sales@liasindustrial.co.uk +44 (0)1204 594941

Flame Scanner Amplifier | 70D40 | Lias Industrial

70D40 / 70D41

Flame switch and manual burner control, Can be used with a variety of flame sensing devices. Fitted to ABB gas turbines.

Description

FIREYE® Series D40-41 Burner Management Controls provide ignition and flame failure protection for manually started oil or gas burners. Plug-in Amplifier Modules permit the selection of ultra- violet, repetitive self-check ultra-violet, AUTOCHECK infrared, or rectification methods of flame detection. The control system includes a safe start check, effective on each start. If flame signal (real or simulated) is detected, the unit cannot be started. For increased safety and reliability, Fireye 72D1R3 AUTOCHECK infrared amplifier (using the pulsing flame signal) and 72DUVS ultraviolet amplifier (using a scanner shutter) check the function of the flame detecting system for component failure during each burner firing cycle. Meter test jacks on each amplifier module provide flame signal readout with a DC voltmeter. Flame failure response time is four seconds (max.). When amplifier modules with T suffix are used, the flame failure response time is reduced to one second (max.).
The control provides three SPDT and one SPNO load switches for external loads and starting circuits. Fireye D40-41 Burner Management controls may be adapted to a simple control system or as a building block with auxiliary devices to provide additional functions.

Available in Atex Enclosure

Use with the following flame scanners

UV1A Non Self Check UV Scanner
45UV5 Self Checking UV Flame scanner
48PT2 Auto Check IR flame scanner

 
 
 

PART NUMBER

DESCRIPTION

MANUAL NUMBER

D SERIES CHASSIS

 

 

70D10

Obsolete - Consult factory

D-1020

70D20

Obsolete - Consult factory

D-1020

70D30

Obsolete - consult factory.

D-30

70D40

Chassis, For manually ignited burners, 120 VAC.

D-4041

70D41

Chassis, For manually ignited burners, 230 VAC.

D-4041

FLAME AMPS

 

 

72D1R1

Infrared auto-check amplifier, 2-4 sec FFRT, use with 48PT2.

D-1020      D-30

72D1R1T

Infrared auto-check amplifier, 1 sec FFRT, use with 48PT2.

D-1020      D-30

72D1R3

Infrared auto-check amplifier (for special application - consult factory), use with 48PT2.

D-1020      D-30

72D1R3T

Infrared auto-check amplifier (for special application - consult factory), 1 sec FFRT, use with 48PT2.

D-1020      D-30

72DRT1

Flame rectification amplifier, 2-4 sec FFRT, use with 45CM or 69ND.

D-1020      D-30

72DRT1T

Flame rectification amplifier, 1 sec FFRT, use with 45CM or 69ND.

D-1020      D-30

72DUV1

Ultraviolet amplifier, 2-4 sec FFRT, use with UV1, UV2, 45UV3.

D-1020      D-30

72DUV1T

Ultraviolet amplifier, 1 sec FFRT, use with UV1, UV2, 45UV3.

D-1020      D-30

72DUVS1

Ultraviolet self-check amplifier, use with 45UV5-1006.

D-1020      D-30

72DUVS1T

Ultraviolet self-check amplifier, 1 sec FFRT, use with 45UV5-1007, -1008, -1009.

D-1020      D-30

72DUVS4

Ultraviolet self-check amplifier, 2-4 sec FFRT, use with 45UV5-1007, -1008, -1009.

D-1020      D-30

Features

This unit can be used as a flame switch only or as a Manual burner control as below:

Part Number

Description

Manual Number

ACCESSORIES FOR CONTROLS AND AMPLIFIERS

7-1040

300MFD capacitor to increase 25SU3-4169T FFRT. - OBSOLETE

CX-784

23-90

Replacement fuse for 25SU3-4169T, -5172, -5173. 1.0 amp.

-

23-93

3.0A fuse for 60-2204-2 (25SU5), 60-2203-2 (25SU3), and 25SU3-2000 (power). See 23-182

-

23-121

Fuse for 60-1706 rack. - OBSOLETE

-

23-173

Replacement fuse for 25SU3-5166, -5168. 1.0 amp.

-

23-182

1.5 A fuse for 25SU3-2100, 2150 (power and RF1), 25SU3-2000 (RF1) and 25SU3-2000 (power) for date codes between 9706 and 9824.

-

23-184

Replacement fuse for 19UVPS and 192SU3.

-

23-194

Replacement fuse for 19MPS, 400 mA.

-

48-1805

Mounting screw for E100, E200, E340, 25SU5-5011, -5166.

-

60-1519

Sensitivity selector plug with cable for 25SU5-4011. - OBSOLETE

CU-13

60-2067

Front panel filler plates (2) for 60-1706 rack. - OBSOLETE

CU-23

60-2203-2

25SU3-5166, -5168 chassis.

CX-742

60-2203-3

25SU3-5167 chassis - OBSOLETE

CX-742

60-2204-2

25SU5-5011, -5012 chassis.

CU-27

60-2205

Display module for 25SU5-5011/50125166/5168.

CU-27 / CX-742

60-2206-1

25SU5-5011, -5012, -5013 wiring base.

-

60-2206-2

25SU3-5166, -5168 wiring base.

-

60-2207-1

Flame amplifier (High sensitivity) for 5011, 5168.

CU-27 / CX-742

60-2207-2

Flame amplifier (High discrimination) for 5012, 5166, 5167.

CU-27 / CX-742

60-2207-3

Flame amplifier (High sensitivity, no hysteresis) for 5013.

CU-27 / CX-742

60-2223

Dust cover.

-

60-2301

Blank display module.

-

60-2367

Ribbon cable for 25SU5-5011/5012/5166/5168.

CU-27 / CX-742

60-2470-1

110 VAC input/24 VDC, 2.5 amps output power supply. Includes 60-2482 connector.

133-566

60-2470-2

220-240 VAC input/24 VDC, 2.5 amps output power supply. Includes 60-2482 connector.

133-566

60-2471-1

Half rack for 25SU3-2000, -2100. Includes one 60-2478 connector.

CU-34

60-2471-3

Full rack for 25SU3-2000, -2100. Includes one 60-2478 connector.

CU-34

60-2478

Screw terminal, straight style (12 AWG) connector for 25SU3-2000, -2100 and 19UVPS.

CU-34

60-2480

Screw terminal, Y style (12 AWG) connector for 25SU3-2000, -2100 and 19UVPS.

CU-34

60-2481

Screw terminal connector for 60-2470, 19MPS.

CU-34

60-2482

Spade terminal connector for 60-2470, 19MPS.

CU-34

60-2490-2

Front filler plate for 60-2471-1, -3. Approx .4" (2 HP).

-

60-2490-4

Front filler plate for 60-2471-1, -3. Approx .8" (4 HP).

-

60-2490-6

Front filler plate for 60-2471-1, -3. Approx 1.2" (6 HP).

-

60-2490-8

Front filler plate for 60-2471-1, -3. Approx 1.6" (8 HP).

-

60-2490-10

Front filler plate for 60-2471-1, -3. Approx 2" (10 HP).

-

60-2530-1

Surface mount rack for use with 25SU3-2000, -2100 amplifier and 19MPS-2000 power supply.

CU-44

60-2530-2

Surface mount rack with hinged clear plastic cover for use with 25SU3-2000, -2100 amplifier and 19MPS-2000 power supply.

CU-44

19MPS-2000

Multi-purpose power supply for 25SU3-2000, -2100 and associated high and low voltage scanners.

CU-45

19UVPS-2120

120 VAC, 19" power supply for 45UV5, 45RM1, and 45RM2 scanners.

CU-38

19UVPS-2220

220 VAC, 19" power supply for 45UV5, 45RM1, and 45RM2 scanners.

CU-38

192SU3-2120

19" adapter (120 VAC) to retrofit 25SU3-2000, -2100 to 60-1706 rack.

CU-36

192SU3-2220

19" adapter (220 VAC) to retrofit 25SU3-2000, -2100 to 60-1706 rack.

CU-36

SIGNAL METERS

 

 

38-54

Flame meter, 2 1/4 inch square, 0-3 VDC, 20K ohm/volt.

-

38-55

Flame meter, horizontal, 0-3 VDC, 20K ohm/volt.

-

38-56

Flame meter, vertical, 0-3 VDC, 20K ohm/volt.

-

38-62

Flame meter, horizontal, 0-3 VDC, 20K ohm/volt. - OBSOLETE

-

38-88

Analog bar graph meter (LED), 0-3 VDC.

CU-24

38-96

Flame meter, 2 1/4 inch square, 4-20 mA.

-

38-97

Flame meter, horizontal, 4-20 mA.

-