sea

Flame Scanner Amplifier | 25SU3-2150 | Lias Industrial

sales@liasindustrial.co.uk +44 (0)1204 594941

Flame Scanner Amplifier | 25SU3-2150 | Lias Industrial

25SU3-2150

Amplifier for use with fireye flame scanners

Description

The 25SU3-2150 is used to detect the presence or absence of a flame in a single or multi-burner environment. It also maximizes burner discrimination with its ability to accurately differentiate the Flame ON and Flame OFF rates produced by the scanners. The 25SU3-2150 has the capacity to receive pulse inputs from two flame scanners, “A” and “B”, either separately or in combination. In addition, it has two logic programs available, called “Scanner Option 1” and “Scanner Option 2.” Within these two scanner options, the user may select different operating parameters, and select the scanner or scanners that will provide the pulse input for that option. Switching between “Scanner Option 1” and “Scanner Option 2” is accomplished by an exter- nal dry contact input to the amplifier. The dynamic range is 1900 pulses per second, which is consis- tent with the output range provided by Fireye scanners. The pulse rate output of each scanner is directly viewed by the user. The design platform of the 25SU3 is based on the global 3U EUROCARD format with the unit oper- ating on either 24 VAC or 24 VDC. Fireye offers full racks and half-racks for mounting, as well as several different power supplies for various scanner/amplifier combinations. See Ordering Informa- tion. The model 25SU3-2150 control includes revised circuitry and is enclosed in a metal case specifi- cally designed to enhance electrical noise rejection. These improvements are realized when the 25SU3-2150 is used with rack connector kit (P/N 61-6898-1) and Fireye four conductor cable (P/N 59-491).

Use with UV Flame scanner 45UV5-1101

Use with IR scanner 45RM4-1003

 

Part Number

Description

Manual Number

CONTROLS AND AMPLIFIERS

25SU3-2000

19 inch rack amplifier, 24 VAC/24VDC. CE Approved.

CU-34E

25SU3-2100

19 inch rack amplifier, 24 VAC/24VDC. FM Approved

CU-34

25SU3-2150

19 inch rack amplifier, 24 VAC/24VDC, high noise immunity CE and FM Approved

CU-54

25SU3-5166

Flame amplifier, 120/230 VAC, high discrimination. Consists of 60-2203-2, 60-2207-2, and 60-2301.

CX-742

25SU3-5166D

Flame amplifier, 120/230 VAC, high discrimination. Consists of 60-2203-2, 60-2207-2, 60-2301, and 60-2205.

CX-742

25SU3-5167

Flame amplifier, 120/230 VAC, high discrimination. No self-checking. Consists of 60-2203-3, 60-2207-2, and 60-2301. - OBSOLETE

CX-742

25SU3-5168

Flame amplifier, 120/230 VAC, high sensitivity. Consists of 60-2203-2, 60-2207-1, and 60-2301.

CX-742

25SU5-5011

Flame amplifier, 120 VAC, high sensitivity. Consists of 60-2204-2, 60-2207-1, and 60-2301.

CU-27

25SU5-5012

Flame amplifier, 120 VAC, high discrimination. Consists of 60-2204-2, 60-2207-2, and 60-2301.

CU-27

25SU5-5013

Flame amplifier, 120 VAC, high sensitivity, no hysteresis. Consists of 60-2204-2, 60-2207-3, and 60-2301.

CU-27

  • Keypad Entry system
  • Password protection to avoid unauthorized alteration of the user-set (programmed) parameters.
  • Eight character alpha-numeric display.
  • Front panel LED Status Indicator.
  • Adjustable Independent Flame Relay Pull-In and Drop-Out Thresholds.
  • Adjustable Flame Failure Response Time (FFRT) (1 to 6 secs.).
  • Adjustable Independent Flame Relay Delay On Time (0 to 10 secs.).
  • Capable of analyzing signals from two scanners.
  • One Form C SPDT Marginal Alarm relay.
  • One fused DPDT Form C Flame relay.
  • One 4 - 20mA analog output (used to measure flame signal—scalable).
  • Remote communications capability to a PLC. Consult factory for details.

Part Number

Description

Manual Number

ACCESSORIES FOR CONTROLS AND AMPLIFIERS

7-1040

300MFD capacitor to increase 25SU3-4169T FFRT. - OBSOLETE

CX-784

23-90

Replacement fuse for 25SU3-4169T, -5172, -5173. 1.0 amp.

-

23-93

3.0A fuse for 60-2204-2 (25SU5), 60-2203-2 (25SU3), and 25SU3-2000 (power). See 23-182

-

23-121

Fuse for 60-1706 rack. - OBSOLETE

-

23-173

Replacement fuse for 25SU3-5166, -5168. 1.0 amp.

-

23-182

1.5 A fuse for 25SU3-2100, 2150 (power and RF1), 25SU3-2000 (RF1) and 25SU3-2000 (power) for date codes between 9706 and 9824.

-

23-184

Replacement fuse for 19UVPS and 192SU3.

-

23-194

Replacement fuse for 19MPS, 400 mA.

-

48-1805

Mounting screw for E100, E200, E340, 25SU5-5011, -5166.

-

60-1519

Sensitivity selector plug with cable for 25SU5-4011. - OBSOLETE

CU-13

60-2067

Front panel filler plates (2) for 60-1706 rack. - OBSOLETE

CU-23

60-2203-2

25SU3-5166, -5168 chassis.

CX-742

60-2203-3

25SU3-5167 chassis - OBSOLETE

CX-742

60-2204-2

25SU5-5011, -5012 chassis.

CU-27

60-2205

Display module for 25SU5-5011/50125166/5168.

CU-27 / CX-742

60-2206-1

25SU5-5011, -5012, -5013 wiring base.

-

60-2206-2

25SU3-5166, -5168 wiring base.

-

60-2207-1

Flame amplifier (High sensitivity) for 5011, 5168.

CU-27 / CX-742

60-2207-2

Flame amplifier (High discrimination) for 5012, 5166, 5167.

CU-27 / CX-742

60-2207-3

Flame amplifier (High sensitivity, no hysteresis) for 5013.

CU-27 / CX-742

60-2223

Dust cover.

-

60-2301

Blank display module.

-

60-2367

Ribbon cable for 25SU5-5011/5012/5166/5168.

CU-27 / CX-742

60-2470-1

110 VAC input/24 VDC, 2.5 amps output power supply. Includes 60-2482 connector.

133-566

60-2470-2

220-240 VAC input/24 VDC, 2.5 amps output power supply. Includes 60-2482 connector.

133-566

60-2471-1

Half rack for 25SU3-2000, -2100. Includes one 60-2478 connector.

CU-34

60-2471-3

Full rack for 25SU3-2000, -2100. Includes one 60-2478 connector.

CU-34

60-2478

Screw terminal, straight style (12 AWG) connector for 25SU3-2000, -2100 and 19UVPS.

CU-34

60-2480

Screw terminal, Y style (12 AWG) connector for 25SU3-2000, -2100 and 19UVPS.

CU-34

60-2481

Screw terminal connector for 60-2470, 19MPS.

CU-34

60-2482

Spade terminal connector for 60-2470, 19MPS.

CU-34

60-2490-2

Front filler plate for 60-2471-1, -3. Approx .4" (2 HP).

-

60-2490-4

Front filler plate for 60-2471-1, -3. Approx .8" (4 HP).

-

60-2490-6

Front filler plate for 60-2471-1, -3. Approx 1.2" (6 HP).

-

60-2490-8

Front filler plate for 60-2471-1, -3. Approx 1.6" (8 HP).

-

60-2490-10

Front filler plate for 60-2471-1, -3. Approx 2" (10 HP).

-

60-2530-1

Surface mount rack for use with 25SU3-2000, -2100 amplifier and 19MPS-2000 power supply.

CU-44

60-2530-2

Surface mount rack with hinged clear plastic cover for use with 25SU3-2000, -2100 amplifier and 19MPS-2000 power supply.

CU-44

19MPS-2000

Multi-purpose power supply for 25SU3-2000, -2100 and associated high and low voltage scanners.

CU-45

19UVPS-2120

120 VAC, 19" power supply for 45UV5, 45RM1, and 45RM2 scanners.

CU-38

19UVPS-2220

220 VAC, 19" power supply for 45UV5, 45RM1, and 45RM2 scanners.

CU-38

192SU3-2120

19" adapter (120 VAC) to retrofit 25SU3-2000, -2100 to 60-1706 rack.

CU-36

192SU3-2220

19" adapter (220 VAC) to retrofit 25SU3-2000, -2100 to 60-1706 rack.

CU-36

SIGNAL METERS

 

 

38-54

Flame meter, 2 1/4 inch square, 0-3 VDC, 20K ohm/volt.

-

38-55

Flame meter, horizontal, 0-3 VDC, 20K ohm/volt.

-

38-56

Flame meter, vertical, 0-3 VDC, 20K ohm/volt.

-

38-62

Flame meter, horizontal, 0-3 VDC, 20K ohm/volt. - OBSOLETE

-

38-88

Analog bar graph meter (LED), 0-3 VDC.

CU-24

38-96

Flame meter, 2 1/4 inch square, 4-20 mA.

-

38-97

Flame meter, horizontal, 4-20 mA.

-