Ignition Systems | Maxfire

Description

The MAXFire® 100 Series gas igniter incorporates the “protected primary combustion zone” design in each of the 5 capacities available. The ignition process starts inside the guide tube away from the burner environment resulting in an extremely stable and reliable igniter. Capacities (nominal) range from 1 mmBtu/hr to 50 mmBtu/hr.

MAXFire® gas igniters provide the most reliable source of energy for main flame ignition, flame stabilization, and boiler warm-up.

Fuel Types

All gas types

Markets Served

All, especially HRSG and utilities

  • Class 1,2 and 3 ignition source
  • Capacity from 50kw to 14Mw
  • Patented protected combustion zone • Flame detection with UV scanner
  • High energy ignition as standard
  • Complete stainless steel construction • Available in any length
  • Diameters from 50mm
  • Near maintenance-free operation
  • Up to 99% reliable ignition 

 

Fuel: Natural gas or propane
Minimum Length: 14 inches
Guide Tube Material: 10 & 30 – Stainless steel
35,40 & 50 – Carbon steel with 12” stainless steel at furnace end

MAXFire 
Model
Capacity 
MBtu/hr
Guide 
Tube OD
Connections (NPT)
Gas Air
Cooling Air 
Requirement*
Nozzle 
Type
Typical Fuel 
Pressure (psig)
110 0.3 to 1.5 1 7/8” 1/2” 3/4” 23 @ 3 Straight 5-12
130 1.5 to 6.0 2 7/8” 3/4” 3/4” 45 @ 3 Straight or wide 5-12
135 5.0 to 15 3 1/2” 1 1/2” 1 1/2” 50 @ 6 Straight or wide 5-25
140 5.0 to 25 4” 1 1/2” 1 1/2” 80 @ 6 Straight or wide 5-25
150 10 to 50 5” TBD TBD 120 @ 6 Straight or wide 5-25

HESI Specifications

Input Voltage: 120 to 240 VAC, 50/60 Hz
Input Power: 120 VAC @ 1.5 A (2-A fuse); 240 VAC @ 0.75A (1-A fuse)
Output Voltage: 2000 VDC
Output Energy: 12 joules per spark
Spark Rate: 3 per second (approximately)
Duty Cycle: 50% at temp 0°F to 135°F (-18°C to 57°C) Ambient

HTSI Specifications

Amperage: 20 mA
Input Voltage: 120 to 240 VAC 50/60 HZ
Output Voltage: 6000 VAC
Duty Cycle: 100% at temperature rating